问题是为什么CPU上的EXTF LED一直亮着。CPU模块信息中存在外部故障。不存在其他故障。
The question is why the EXTF LED at the CPU is lit on all the time. External Fault present within CPU module information. No other faults present.
在硬件配置中,所有网元都正常。在在线拓扑中,唯一的红色标记元素是CPU。另请参阅随附的诊断缓冲区上载。
Within Hardware Configuration all network elements are healthy. Also within online topology the only red marked element is the CPU. Please also see attached the upload of the diagnostic buffer.
CPU详细信息:CPU 416F-3 PN/DP,416-3FS07-0AB0,V7.0.0。
Details of the CPU: CPU 416F-3 PN/DP, 416-3FS07-0AB0, V7.0.0.
我如何了解外部故障存在的原因?
How can I learn the reason of External Fault being present?
你好,kjanda75,
hi kjanda75,
CPU连接了什么?
what is connected to the CPU?
这是外部故障。也许硬件中有Profibus或Profinet投影,但没有任何连接。
this is an external fault. Maybe there is a Profibus or Profinet projected in HW and there´s nothing connected.
致问候,
regards,
你好mopS04
Hi mopS04
感谢您的回复。因此,Profibus和Profinet网络都是健康的。Profinet拓扑也正常。
Thanks for reply. So there are both - Profibus and Profinet networks, both are healthy. Profinet topology healthy as well.
与此同时,我的同事联系了西门子,得知问题可能是配置的PN/PN耦合器版本(v2.0)和物理连接的版本(v3.0)之间存在差异。
In the meantime my colleague contacted Siemens, was advised that possibly the problem is in discrepancy between version of PN/PN coupler configured (v2.0) and physically connected (v3.0).
由于我们整天都在制作,所以我们只有在周六才有机会下载硬件配置。
As we have production all day and night we will have opportunity to download HW-Config only on Saturday.
我希望问题出在PN/PN耦合器配置中,奇怪的是没有总线故障
I hope the problem is in PN/PN coupler configuration, strange is there is no Bus fault
...,这意味着没有故障指示灯亮起。但PLC 2处于故障状态,EXTF指示灯亮着。我们已经尝试了以下操作,但没有成功。 we have commissioned a S7-400H station CPU 417-5H. Here we find a situation where all the components in the Profinet network are OK and PLC 1 is good...
...on System, CPU SpecificationsRUN,STOP闪烁2Hz:CPU为DFEKTIVE。INTF、EXTF、FRCE、BUSF1、BUSF5和IFM1F LED也闪烁。 2Hz blinking of RUN,STOP: CPU is DFEKTIVE. The INTF,EXTF,FRCE,BUSF1,BUSF5 and IFM1F LED´s also flash.希望这能有所帮助, hope this helps,regards, regards,推荐...
...0系统。 I am working on S7-400 system for the first time.CPU 414-2显示EXTF和INTF LED闪烁。cpu上没有其他LED闪烁。 There is CPU 414-2 which is showing both the EXTF & INTF LED's blinking. No other LED is blinking on the cpu.我无法与CPU 414-2通信。 I am unable to communicate...
...这些天我面临着问题,我的PLC西门子Simatic S7-400 Cpu GivingEXTF.在打开/关闭CPU故障清除后,但我想知道为什么会发生这种情况,以及我们如何预防这种故障。 i am facing problem in these days, My PLC Siemens Simatic S7-400 Cpu Giving EXTF.After ON/Off CPU...
...拉茨23。 Pratts23.推荐答案2您好, Hi,强制DO不应导致任何EXTF或SF。你能上传诊断缓冲区吗 Forcing DO should not cause any EXTF OR SF. Could you upload diagnostic buffer维杰 Vijay推荐答案3你好, Hello,请勿在强制期间将CPU视为正常工作 Do not treat the ...
...figuraton to another 414-5h cpu, but its not going to RUN mode. with STOP, EXTF, REDF Led's ON. (Event error code 16#5961 "Parameter assignment error ")没有连接从设备,那么这些Led的原因可能是什么;s There is no slave connected, Then what may be the reason for these Led;sPlz Help...
...fig时,所有DP-Slave也都有红色的X标记。正如我注意到的,EXTF LED亮起,BUS2F和IFM1F两个LED都闪烁。你能帮我做这件事吗。 I'm facing some problem here and I need your help/advice. Currently I'm using CPU414-3 and CPU414-2 as my DP master. Already downloaded the pro...
...此同时,您有2个诊断CPU上的LED激活:STOP(RUN未激活)和ExtF In the meantime, you have 2 diagnostic LEDs active on the CPU: STOP (with RUN not active) and ExtF.B基于S7-400 CPU规格手册: Based on the S7-400 CPU specifications manual:https://support.industry.siemens.com/cs/ww/...
问题描述大家好, Hi guys,我有这个问题,导致CPU中的连续Extf处于运行模式,我只有一个疑问,在我的硬件库中,我的CPU CP 443-1 1EX11-0XE0只有2.6固件版本,但我有2.7!!我更新了硬件库,但它没有出现!!有什么建议吗? I have this...
...07-01AB0不存在了,6ES74十四-3FM07-0AB0可用我们可以通过更改CPU订单号为HW Config来加载和运行6ES7414-3FM07-0AB0上的程序吗??? Can we use 6ES7414-3FM07-0AB0 instead of 6ES7414-3EM07-0AB0.Our 6ES7414-3EM07-0AB0 is gone and 6ES7414-3FM07-0AB0 is available.Can we load...
如果觉得我的文章对您有用,请随意打赏。你的支持将鼓励我继续创作!