问题描述

大家好,

Hi All,

S7-400机架是否有profibus耦合器?

Is there any profibus coupler for S7-400 racks?

顺致敬意,

Best regards

阿扎德

Azad

推荐答案2

你好,阿扎德;

Hello Azad;

S7-400机架没有Profibus从机IM,例如S7-300/ET 200M(IM 153-2)或ET 200S(IM 151-1)。

There are no Profibus slave IMs for S7-400 racks, such as exists for the S7-300/ET 200M (IM 153-2) or ET 200S (IM 151-1).

以下屏幕截图显示了在扩展配置中使用S7-400机架的唯一方法,摘自S7-400模块数据手册第6章“接口模块:

The only way to use a S7-400 rack in an expansion configuration is shown in the screenshot below, extacted from the S7-400 Module data manual, chapter 6, Interface Modules:

https://support.industry.siemens.com/cs/ww/en/view/1117740

https://support.industry.siemens.com/cs/ww/en/view/1117740

您还可以从另一个自动化论坛查看此讨论的内容:

You could also look at the contents of this discussion, from another automation forum:

http://forums.mrplc.com/index.php?/topic/13729-s7-400-dp-slave-模块/

http://forums.mrplc.com/index.php?/topic/13729-s7-400-dp-slave-module/

希望这能有所帮助,

Hope this helps,

丹尼尔·查蒂尔

Daniel Chartier

你可能感兴趣的文章

Y_LINK输入PLC

...face to a redundant H system.Y链路由两个IM 153-2接口模块和一个Y合器组成。 The Y link consists of two IM 153-2 interface modules and a Y coupler.Y链路通过接口模块连接到冗余DP主系统。远程IO设备通过Y合器连接到Y链路,即: The Y link is connected...

  • 发布于 2022-10-11 11:55
  • 阅读 ( 134 )

S7-400H安装架

...ge in doing it this way?备选方案是什么?。。模块能否更改为Profibus连接单元? What is the alternatives?.. can the modules change to Profibus connected units?.. ..致我们新朋友杰西·菲达——如果可能话, To our new friend Jlassi Fida - if at all possible, ...

  • 发布于 2022-10-11 12:03
  • 阅读 ( 177 )

Simatic硬件目录更新

...。不幸是,现有目录中没有提供所有必需模块(Im和Y合器)。你能帮我更新一下硬件目录吗?如果我更新了目录,现有目录不会受到影响吗?更新目录只能在我EWS中完成,不能在CPU中下载? Im trying to do hardware configurat...

  • 发布于 2022-10-11 12:14
  • 阅读 ( 133 )

新硬件设备连接

... the attachment, explained in the following manual:SIMATIC总线链接DP/PA合器、有源磁场分配器、DP/PA链路和Y链路 SIMATIC Bus links DP/PA coupler, active field distributors, DP/PA Link and Y Linkhttps://support.industry.siemens.com/cs/ww/en/view/1142696 https://support.industry.si...

  • 发布于 2022-10-11 16:29
  • 阅读 ( 126 )

如何在冗余配置中配置Profibus DP合器

...望在PLC/DCS和他们DCS(同样是西门子S7 400H)之间使用DP合器进行一些数据交换。他们还需要冗长沟通。如何在冗余模式下安装和配置Profibus DP合器提前感谢大家回答--问候, Dear All,We have one S7 414-5H redundant system with redunda...

  • 发布于 2022-10-11 12:56
  • 阅读 ( 362 )

集成

...使用IM 153-2或IM-153-4接口模块,轻松地将S7-300 I/O模块作为Profibus DP或Profinet从设备“集成”到S7-400 CPU,。 However, you can easily "integrate" S7-300 I/O modules as Profibus-DP or Profinet slaves to the S7-400 CPUs, as part of a ET 200M system, with a IM 153-2 or IM-15...

  • 发布于 2022-10-11 17:59
  • 阅读 ( 113 )

S7-400H冗余故障

...敬用户:, Dear User,如果您使用适当ET200M模块,用于PROFIBUS子网和所有available .如果BUSF2闪烁,您需要识别S7-400H系统上故障从机/连接器。如果我们松开了F.O连接,就会出现这种情况。 It is unlikely to happen if you are using a proper E...

  • 发布于 2022-10-11 19:28
  • 阅读 ( 172 )

400H冗余问题,无法从PLC 1切换到PLC2 I/O地址诊断错误

...止模式或关闭时,第二个PLC不会进入运行模式。连接到Y合器从属设备在诊断缓冲器中没有任何问题,但我确实对连接到PLC 1其他Profibus设备地址有问题。因此,在诊断缓冲区警报中显示了硬件配置图中所示PLC 2网络A和D...

  • 发布于 2022-10-11 20:04
  • 阅读 ( 178 )

总线2f错误

... other way.-当CPU操作系统检测到连接CPU和远程I/O站(例如Profibus或Profinet)网络上错误时,会出现BusXf LED。节点接口或模块、电缆接头故障可能是故障源。 - the BusXf LED appears when the operating system of the CPU detects an error on the networ...

  • 发布于 2022-10-11 20:36
  • 阅读 ( 175 )

S7-400 CPU更换S7-300 CPU

...IM 153-2轻松更换S7-300 CPU,将S7-300机架和I/O模块转换为一个Profibus DP从机,您可以连接到S7-400集成Profibus主端口。 You have an option to re-use the I/O modules: you can easily replace the S7-300 CPU with a  IM 153-1 or IM 153-2, transforming the S7-300 rack and I/O mo...

  • 发布于 2022-10-11 21:28
  • 阅读 ( 119 )