嗨,各位,
Hi Guys,
我再次需要你的专业知识,我现在有这个问题,这是相当阻碍我继续发展这个项目。
Once again I need your expertise, I have this problems just now and it is quite hindrance for me to proceed on developing the project.
这些问题发生在我下载我制作的HW Configured后,我将详细阐述。
The issues take place after I download the HW Configured I made, which I will elaborate in details.
第一个硬件配置
First HW Config
-它包括机架、2个用于冗余的PS和2个CPU(CPU 0作为主CPU,CPU1作为备用CPU)
- It consists of Racks, 2 PS for redundancy and 2 CPU (CPU 0 as Master and CPU1 as Stand by)
-按照目录号将其插入SIMATIC MANAGER V5.5中的硬件配置,然后保存并编译,最后下载到CPU 0。
-By inserting it to HW Config in SIMATIC MANAGER V5.5 as per catalog number then save and compile and last download it to the CPU 0.
-无错误发生,系统平稳。当我检查OPERATIONAL MODE(操作模式)时,它清楚地表明REDUNDANT(冗余)处于RUN MODE(运行模式)。CPU 0也处于RUN MODE(运行模式),CPU 1也是如此。
-No ERROR OCCURS and SYSTEM is smooth. As I check the OPERATIONAL MODE it was clearly indicated that the REDUNDANT is in RUN MODE. CPU 0 is also in RUN MODE and so as to the CPU 1.
现在是有趣的部分。。。
Now here is the fun part...
-我现在将ET200M插入PROFIBUS冗余。
-I will now insert my ET200M in PROFIBUS REDUNDANCY.
-IM(1)连接在PROFIBUS DP 1中,IM(2)连接在PROFIBUS DP 2中。(根据目录)
-IM(1) is connected in PROFIBUS DP 1 and IM(2) in connected in PROFIBUS DP 2.( as per catalog)
-将SM信号模块(DI)插入ET 200M。
-insert a SM signal module (DI) to the ET 200M.
-保存和编译后不会发生错误。
-After save and compile no error occur.
-然而,当i下载到CPU 0后,CPU1发生总线故障错误,REDF为LIT。
-HOWEVER, after i DOWNLOADED to the CPU 0, ther BUS FAULT error occur in CPU1 and the REDF is LIT.
-CPU 1的BUS FAULT(总线故障)正在闪烁,起初我们认为问题出在PROFIBUS电缆上。因此,我们使用了CPU 0中使用的PROFIBUS电缆。
-The BUS FAULT at CPU 1 is flashing, at first we thought that the problem was in the PROFIBUS CABLE. So we used the PROFIBUS CABLE used in CPU 0.
结果仍然是相同的CPU 0平稳运行,而CPU 1仍存在总线故障。。。。
The result is still the same CPU 0 is running smoothly, while the CPU 1 still on bus fault....
各位,任何你想分享的技术总结……因为这个问题,我无法继续我的项目。。
GUYS ANY TECHNICAL RECCOMENDATION you want to share...I cant proceed to my project because ot this ISSUES..
非常感谢你来适应。
Thank you so much in ADAVANCE.
谨致问候,
Sincerely yours,
MICOY公司
MICOY
故障排除:
Troubleshooting:
检查光纤电缆是否同步正常。当我通过拨动开关停止CPU 0时,它将其主功能转移到CPU 1。
Check the fiber optic cable for synchronization OKAY, When I stop the CPU 0 by means of toggle switch it transfer its MASTER function to CPU 1.
HW配置ET 200M,并将其仅连接到CPU 0,DP线正常,无错误发生。
HW config ET 200M, and connect it to CPU 0 only, DP line okay and no error occur.
HW配置ET 200M并将其仅连接到CPU 1,DP线也正常,没有发生错误…这使我感到头晕目眩。这很令人困惑。在独立CPU配置中,其PROFIBUS DP工作,但在冗余配置中,CPU 1 DP LINE始终不工作。。。。
HW config ET 200M and connect it to CPU 1 only, DP line ALSO OKAY, no error occur...This make my spin head. It is quite confusing..In a stand alone CPU config its PROFIBUS DP works, But in redundant configuration, always CPU 1 DP LINE is not functioning....
帮帮我PLZ。。。。
HELP ME PLZ....
[quote user=“micoy”]大家好,
[quote user="micoy"]Hi Guys,
我再次需要你的专业知识,我现在有这个问题,这是相当阻碍我继续发展这个项目。
Once again I need your expertise, I have this problems just now and it is quite hindrance for me to proceed on developing the project.
这些问题发生在我下载我制作的HW Configured后,我将详细阐述。
The issues take place after I download the HW Configured I made, which I will elaborate in details.
第一个硬件配置
First HW Config
-它包括机架、2个用于冗余的PS和2个CPU(CPU 0作为主CPU,CPU1作为备用CPU)
- It consists of Racks, 2 PS for redundancy and 2 CPU (CPU 0 as Master and CPU1 as Stand by)
-按照目录号将其插入SIMATIC MANAGER V5.5中的硬件配置,然后保存并编译,最后下载到CPU 0。
-By inserting it to HW Config in SIMATIC MANAGER V5.5 as per catalog number then save and compile and last download it to the CPU 0.
-无错误发生,系统平稳。当我检查OPERATIONAL MODE(操作模式)时,它清楚地表明REDUNDANT(冗余)处于RUN MODE(运行模式)。CPU 0也处于RUN MODE(运行模式),CPU 1也是如此。
-No ERROR OCCURS and SYSTEM is smooth. As I check the OPERATIONAL MODE it was clearly indicated that the REDUNDANT is in RUN MODE. CPU 0 is also in RUN MODE and so as to the CPU 1.
现在是有趣的部分。。。
Now here is the fun part...
-我现在将ET200M插入PROFIBUS冗余。
-I will now insert my ET200M in PROFIBUS REDUNDANCY.
-IM(1)连接在PROFIBUS DP 1中,IM(2)连接在PROFIBUS DP 2中。(根据目录)
-IM(1) is connected in PROFIBUS DP 1 and IM(2) in connected in PROFIBUS DP 2.( as per catalog)
-将SM信号模块(DI)插入ET 200M。
-insert a SM signal module (DI) to the ET 200M.
-保存和编译后不会发生错误。
-After save and compile no error occur.
-然而,当i下载到CPU 0后,CPU1发生总线故障错误,REDF为LIT。
-HOWEVER, after i DOWNLOADED to the CPU 0, ther BUS FAULT error occur in CPU1 and the REDF is LIT.
-CPU 1的BUS FAULT(总线故障)正在闪烁,起初我们认为问题出在PROFIBUS电缆上。因此,我们使用了CPU 0中使用的PROFIBUS电缆。
-The BUS FAULT at CPU 1 is flashing, at first we thought that the problem was in the PROFIBUS CABLE. So we used the PROFIBUS CABLE used in CPU 0.
结果仍然是相同的CPU 0平稳运行,而CPU 1仍存在总线故障。。。。
The result is still the same CPU 0 is running smoothly, while the CPU 1 still on bus fault....
各位,任何你想分享的技术总结……因为这个问题,我无法继续我的项目。。
GUYS ANY TECHNICAL RECCOMENDATION you want to share...I cant proceed to my project because ot this ISSUES..
非常感谢你来适应。
Thank you so much in ADAVANCE.
谨致问候,
Sincerely yours,
MICOY公司
MICOY
故障排除:
Troubleshooting:
检查光纤电缆是否同步正常。当我通过拨动开关停止CPU 0时,它将其主功能转移到CPU 1。
Check the fiber optic cable for synchronization OKAY, When I stop the CPU 0 by means of toggle switch it transfer its MASTER function to CPU 1.
HW配置ET 200M,并将其仅连接到CPU 0,DP线正常,无错误发生。
HW config ET 200M, and connect it to CPU 0 only, DP line okay and no error occur.
HW配置ET 200M并将其仅连接到CPU 1,DP线也正常,没有发生错误…这使我感到头晕目眩。这很令人困惑。在独立CPU配置中,其PROFIBUS DP工作,但在冗余配置中,CPU 1 DP LINE始终不工作。。。。
HW config ET 200M and connect it to CPU 1 only, DP line ALSO OKAY, no error occur...This make my spin head. It is quite confusing..In a stand alone CPU config its PROFIBUS DP works, But in redundant configuration, always CPU 1 DP LINE is not functioning....
帮帮我PLZ。。。。
HELP ME PLZ....
你好,普拉纳夫,
Hi Pranav,
感谢您的回复,是的,我为我的2 IM设置了相应的PROFIBUS ID。截至目前,我仍在排除可能的原因。
Thanks for the reply, Yes I do set the corresponding PROFIBUS ID for my 2 IM. As of this moment, I am still troubleshooting what might be the possible cause.
这让我头晕目眩,我的硬件配置没有任何问题,我按照CAT#插入了所有项目,此外,我还尝试切换PROFIBUS电缆。然而,同样的情况也发生了。
It make my head spin, I haven't seen any problem about my HW configuration I insert all the items as per CAT# and moreover, I have tried to switch the PROFIBUS CABLE. Yet still, same scenario occurs.
然而,事情发生了变化。昨天,我的问题是CPU 1(备用)Profibus 2网络,此时它被改为CPU 0(主)Profibus1网络。。。
However, a change of things happen. Yesterday, my issue was the CPU 1 (stand by) Profibus 2 network, at this very moment it was change to CPU 0 (master) Profibus 1 network...
真奇怪,你能帮我吗…谢谢。。
This is weird can you help me.. Thanks..
后续问题发布者vrk与主题分割为单独的线程将数据从硬件冗余cpu发送到软件冗余cpu.
Follow up question published by vrkis split to a seperate thread with the subjectsend data from Hardware redundancy cpu to software redundancy cpu.
顺祝商情主持人
Best regards CS Moderator
...但我认为发生的情况是,有时与两个CPU的通信中断,您的profibus从站出现故障。原因可能是现场总线电缆附近的强电流电缆在每次电机启动时都会造成干扰,现场总线绞线的端接不正确,现场总线电缆过长。如果找不到任何原因...
问题描述尊敬的各位:, Dear All,我安装了CPU 414-3DP。在Profibus上网络连接了多个从设备。节点配置在硬件配置,但不在编程中使用。这是一个非西门子卡。由于该节点硬件问题,PLC显示总线故障。PLC是运行时,总线故障闪烁。 I...
...ge in doing it this way?备选方案是什么?。。模块能否更改为Profibus连接单元? What is the alternatives?.. can the modules change to Profibus connected units?.. ..致我们的新朋友杰西·菲达——如果可能的话, To our new friend Jlassi Fida - if at all possible, ...
...接连接到I/O机架,以获得I/O冗余 andconnectdirectly each two cpu profibus conector to I/O rackwithtwo IM 153-2 for have I/Oredundancy这是正确的工作吗? is it acorrect work?谢谢和问候 Thanks & Regards推荐答案2这是正确的,但请记住使用IM中的DIP开关对具...
...tten from the automation system to the measuring via:•现场总线PA • PROFIBUS PA•基金会现场总线 • FOUNDATION Fieldbus 所有这些连接都可用于S7-400H系统;我更熟悉Profibus-PA。对于此现场总线,您可以使用附件中所示的冗余连接类型,如以下手册...
问题描述尊敬的专家:, Dear Experts,我有S7400 H CPU 417,机架0正在运行,机架1处于停止模式(冗余故障)。加载内存已满-每次请求内存压缩。允许的最大内存字节数是32768,修改后使用的是29696。 I have S7400 H CPU 417, Rack 0 is running an...
...(物理上是最后一个),则您可能会面临终端问题。检查Profibus连接器上的端接电阻器是否激活,在最坏的情况下,更换一个新的连接器并激活电阻器。如果总线上没有终端,则Profibus信号的反射会通过总线传输并破坏传输的数...
...ween Sync Modules and download OB72 in H System.同时检查冗余CPU上的Profibus DP连接器、电缆和总线终端DIP开关 Also Check Profibus DP Connector, Cables and Bus Termination DIP Switch on Redundant CPU.推荐答案3Kamath RL发布的新问题与主题分为单独的线程为什么...
...敬的用户:, Dear User,如果您使用适当的ET200M模块,用于PROFIBUS子网和所有available .如果BUSF2闪烁,您需要识别S7-400H系统上的故障从机/连接器。如果我们松开了F.O连接,就会出现这种情况。 It is unlikely to happen if you are using a proper E...
...S 7环境中,您可以使用Compact FF Link(IM 655‑5 FF)作为FF的Profibus DP扩展: To my knowledge, it is possible to use FF H1 with S7-400H CPUs, but only as part of PCS 7 environment, It wll not work with Step 7/WnCC. In a PCS 7 evironment, you can use the Compact FF Link (IM 655‑5 ...