你好
hello.........,
前一段时间,我买了一个带一些模块的机架来尝试一些东西。它是一个314 ifm。其中一个模块是cp340rs422/485。我对这个模块很着迷,我想了解更多关于它的信息,我在网上找到了一些关于它的教程。但不知怎的,我的项目行不通。虽然我在同一个机架上购买了314和cp340,但我感觉cp340在314 ifm上不起作用,“它不兼容”。
some time ago i bought a rack with some modules to try something out. its a 314 ifm . one of the modules is a cp340 rs422/485. fascinated by this module i want to know more about it and i found some tutorial about it on the internet. but somehow my project doesnt work. and although i bought the 314 and cp340 together on the same rack, i get the sense that the cp340 doesn't work on an 314 ifm, " it's not compatible" or so.
但我在这个论坛上搜索了它是否兼容,我没有得到一个决定性的答案
but i was searching on this forum if it's compatible or not, i don't get a decisive answer.
任何在314上使用cp340的人
anyone experience with a cp340 on a 314
gr杰拉德
gr gerard
你好,杰拉德;
Hello Gérard;
为了建立兼容性,我们需要关于CPU 314 IFM和CP 340的部件号和固件信息。
To establish compatibility we would need part number and firmware information on the CPU 314 IFM and the CP 340.
您可以在模块的铭牌信息(右侧)上找到它,在HWConfig编辑器中,您可以检查是否为项目选择了这些确切的版本。
You can find it on the nameplate information of the modules (on the right side), and in the HWConfig editor you can check if these exact versions have been selected for the project.
希望这有帮助,
Hope this helps,
丹尼尔·查蒂尔
Daniel Chartier
你好,丹尼尔
hello daniel
cpu 314ifm 314-5ae03-0ab0 v1.0.0
cpu 314ifm 314-5ae03-0ab0 v1.0.0
cp340 rs422/485 340-1ch00-0ae0
cp340 rs422/485 340-1ch00-0ae0
gr杰拉德
gr gerard
你好,杰拉德;
Hello Gérard;
关于CPU 314 IFM的信息很难获得,即使是在西门子产品支持部门,因为它自2002年起已被淘汰(自2012年起完全停止)。。
Information on the CPU 314 IFM is hard to come by, even on the Siemens Product Support, since it has been phased-out since 2002 (and totally discontinued since 2012)..
然而,我找到了可能感兴趣的文件:
However I have located this document that could be of interest:
在哪个CPU中可以可变地寻址CP340和CP341
In which CPU can you variably address CP340 and CP341?
https://support.industry.siemens.com/cs/ww/en/view/42989
https://support.industry.siemens.com/cs/ww/en/view/42989
措辞不是很清楚,但我将其解释为将CPU314 IFM与CP340的兼容版本限制为比您的固件更高的版本。所以您的应用程序不应该像您自己测试的那样工作。
The wording is not very clear, but I interpret it as limiting the compatible versions of CPU 314 IFM with a CP 340 to versions of a later firmware than yours. so your application should not work, as you tested yourself.
下表列出了该变量寻址是不可能的。在这些CPU中,寻址取决于模块插槽。
The following table lists the older CPUs in which variable addressing is not possible. In these CPUs addressing depends on the module's slot.
CPU 314 IFM CPU 314 IFM | 6ES7314-5AE0x-0AB0 6ES7314-5AE0x-0AB0 | 所有1.2版及以下版本 all up to and including V 1.2 |
如果您需要更多(更决定性的)信息,您必须使用支持请求(本页顶部的链接)直接联系西门子技术人员。
If you need further (and more decisive) information, you would have to go directly to Siemens techs, using a Support request (link at the top of this page).
希望这有帮助,
Hope this helps,
丹尼尔·查蒂尔
Daniel Chartier
丹尼尔,
daniel,
谢谢
thanks,
我还认为我的314ifm无法工作,所以我尝试了我的315,在硬件配置过程中,我注意到一些东西(见附件)红色箭头指向了我不确定的东西,它给我的感觉是有些东西不正常。如果我按ctrl+d,一切都好了。它可能是什么,我如何才能发现
i also think that my 314ifm won't work so i try my 315, during hardware configuration i notice something (see attachement) red arrow is pointing to something i'am not sure with, it gives me the sense that there is something not oke. if i press ctrl+d everything is oke. what can it be and how can i find out
gr杰拉德
gr gerard
你好,杰拉德;
Hello Gérard;
在HWConfig编辑器的在线视图中,诊断符号将显示CPU、CP、FM…的状态信息。。。
In the online view of the HWConfig editor, diagnostic symbols will appear showing status information on the CPU, CP, FM...
您指向的菱形符号表示您的CPU处于运行模式,没有诊断。所以现在一切都很好。
The diamond symbol you point to states that your CPU is in RUN mode, without diagnostics. So all is well at this time.
这些符号在安装步骤7的计算机的Simatic/Documentation目录中的“步骤7编程诊断”手册一章中进行了描述。
These symbols are described in the chapter on Diagnostics of the Programming with Step 7 manual, which you will find in the Simatic/Documentation directory of the computer where you have installed Step 7.
或者,您可以从产品支持页面的以下链接下载:
Alternatively you can download it from the Product Support page, on this link:
https://support.industry.siemens.com/cs/ww/en/view/45531107
https://support.industry.siemens.com/cs/ww/en/view/45531107
希望这有帮助,
Hope this helps,
丹尼尔·查蒂尔
Daniel Chartier
...ly replacement of this. 推荐答案2你好 Hello,你为什么认为这个货架已经停产了? why you think the rack is discontinued?在西门子MAll中是PM300“活跃产品”,在机架的技术信息中也没有关于中断的信息。 In the Siemens MAll is PM300 "active product" and in...
...障6ES7414-1XG01-0AB0,西门子不再提供或支持它。我可以购买二手单元,但由于我位于澳大利亚,而相关单元位于欧洲,因此接收将延迟。澳大利亚eBay上有一款6ES7414-2XG03-0AB0,但我想在花费$之前确定兼容性。如果有人能回复我,让...
...它通电,像你的帖子一样出现错误。或者您刚购买了一台二手m/c,当您打开包装时,它将首次通电 2nd--Let me know the story of your m/c--such as it is your daily using production m/c, running good in last week, yesterday morning you power up it, you get error like yo...
...营m/c几年是不错的,还是你刚从前店主那里得到了它作为二手m/c,如果以后你在它来到你面前之前就知道它运转得很好。命名m/c构建器。 and can you let forum know a more detail story of your m/c--is it good running m/c in your shop for couple of years or ...
如果觉得我的文章对您有用,请随意打赏。你的支持将鼓励我继续创作!